Getting Started

  1. Log on to windows terminal in the online network.
  2. Open the directory G:\online\ecs\NewShortcuts\VELO
  3. Double click on VEDCSHV_UI_FSM
  4. The following window appears:
Changed:
<
<
VEDCSHV_UI_FSM.PNG
>
>
VEDCSHV_UI_FSM.PNG

 
  1. To operate a module on the C side rightclick on VELOC_DCS
Changed:
<
<
VELOC_DCS_TOP.PNG
>
>
VELOC_DCS_TOP.PNG

 
  1. Take control of the project by left clicking on the padlock next to VELOC_DCS on the panel and then clicking Take in the panel which appears.
Changed:
<
<
VELOC_DCS_TAKE.PNG
>
>
VELOC_DCS_TAKE.PNG

 
  1. Double click on the VELOC_DCS_LV button.
  2. The following panel should appear:
Changed:
<
<
VELOC_DCS_LV_TOP.PNG
>
>
VELOC_DCS_LV_TOP.PNG

 
  1. If the button next to VELOC_DCS_LV_ConfDB is NOT_READY then click this button.
Changed:
<
<
VELOC_DCS_LV_ConfDB.PNG
>
>
VELOC_DCS_LV_ConfDB.PNG

 
  1. The following panel should appear. Click Send PHYSICS.
Changed:
<
<
VELOC_DCS_LV_ConfDB_PHYSICS.PNG
>
>
VELOC_DCS_LV_ConfDB_PHYSICS.PNG

 
  1. The panel should now look like this:
Changed:
<
<
VELO_DCS_LV_OFF.PNG
>
>
VELO_DCS_LV_OFF.PNG

 
  1. Switch on the 48V supply - click on button next to VELOC_DCS_LV_PS
Changed:
<
<
VELOC_DCS_LV_PS.PNG
>
>
VELOC_DCS_LV_PS.PNG

 
  1. Send the RUN_TYPE PHYSICS.
Changed:
<
<
VELOC_DCS_LV_PS_PHYSICS.PNG
>
>
VELOC_DCS_LV_PS_PHYSICS.PNG

 
  1. VELOC_DCS_LV_PS should now be READY.
Changed:
<
<
VELOC_DCS_LV_PS_READY.PNG
>
>
VELOC_DCS_LV_PS_READY.PNG

 

-- MarkTobin - 06 Aug 2008

Revision 52008-08-06 - MarkTobin

Line: 1 to 1
 
META TOPICPARENT name="VELOLVBasic"

Getting Started

  1. Log on to windows terminal in the online network.
Changed:
<
<
  1. Open the directory G:\online\ecs\Shortcuts\VELO
>
>
  1. Open the directory G:\online\ecs\NewShortcuts\VELO
 
  1. Double click on VEDCSHV_UI_FSM
  2. The following window appears:
    VEDCSHV_UI_FSM.PNG
Line: 12 to 12
  VELOC_DCS_TAKE.PNG
  1. Double click on the VELOC_DCS_LV button.
  2. The following panel should appear:
Changed:
<
<
VELOC_DCS_LV_TOP.PNG
>
>
VELOC_DCS_LV_TOP.PNG
 
  1. If the button next to VELOC_DCS_LV_ConfDB is NOT_READY then click this button.
Changed:
<
<
VELOC_DCS_LV_ConfDB.PNG
>
>
VELOC_DCS_LV_ConfDB.PNG
 
  1. The following panel should appear. Click Send PHYSICS.
Changed:
<
<
VELOC_DCS_LV_ConfDB_PHYSICS.PNG
>
>
VELOC_DCS_LV_ConfDB_PHYSICS.PNG
 
  1. The panel should now look like this:
Changed:
<
<
VELO_DCS_LV_OFF.PNG
>
>
VELO_DCS_LV_OFF.PNG
 
  1. Switch on the 48V supply - click on button next to VELOC_DCS_LV_PS
Changed:
<
<
VELOC_DCS_LV_PS.JPG
>
>
VELOC_DCS_LV_PS.PNG
 
  1. Send the RUN_TYPE PHYSICS.
Changed:
<
<
VELOC_DCS_LV_PS_PHYSICS.PNG
>
>
VELOC_DCS_LV_PS_PHYSICS.PNG
 
  1. VELOC_DCS_LV_PS should now be READY.
Changed:
<
<
VELOC_DCS_LV_PS_READY.PNG
>
>
VELOC_DCS_LV_PS_READY.PNG
 
Changed:
<
<
-- MarkTobin - 29 Apr 2008

META FILEATTACHMENT attachment="VELOC_DCS_LV_PS.JPG" attr="" comment="" date="1207148465" name="VELOC_DCS_LV_PS.JPG" path="VELOC_DCS_LV_PS.JPG" size="115931" stream="VELOC_DCS_LV_PS.JPG" user="Main.MarkTobin" version="1"
>
>
-- MarkTobin - 06 Aug 2008

Revision 42008-06-23 - MarkTobin

Line: 1 to 1
 
META TOPICPARENT name="VELOLVBasic"

Getting Started

  1. Log on to windows terminal in the online network.
Line: 7 to 7
 
  1. The following window appears:
    VEDCSHV_UI_FSM.PNG
  2. To operate a module on the C side rightclick on VELOC_DCS
Changed:
<
<
VELOC_DCS_TOP_ERROR.PNG
ALERT! ERROR state for LV is normal when 48V supply is off ALERT!
>
>
VELOC_DCS_TOP.PNG
 
  1. Take control of the project by left clicking on the padlock next to VELOC_DCS on the panel and then clicking Take in the panel which appears.
    VELOC_DCS_TAKE.PNG
  2. Double click on the VELOC_DCS_LV button.

Revision 32008-04-29 - MarkTobin

Line: 1 to 1
 
META TOPICPARENT name="VELOLVBasic"

Getting Started

  1. Log on to windows terminal in the online network.
  2. Open the directory G:\online\ecs\Shortcuts\VELO
  3. Double click on VEDCSHV_UI_FSM
Changed:
<
<
  1. The following window appears: VEDCSHV_UI_FSM.JPG
>
>
  1. The following window appears:
    VEDCSHV_UI_FSM.PNG
 
  1. To operate a module on the C side rightclick on VELOC_DCS
Changed:
<
<
VELOC_DCS_TOP.JPG
  1. Take control of the project by clicking on the padlock next to VELOC_DCS on the panel.
    VELOC_DCS_TAKE.JPG
>
>
VELOC_DCS_TOP_ERROR.PNG
ALERT! ERROR state for LV is normal when 48V supply is off ALERT!
  1. Take control of the project by left clicking on the padlock next to VELOC_DCS on the panel and then clicking Take in the panel which appears.
    VELOC_DCS_TAKE.PNG
 
  1. Double click on the VELOC_DCS_LV button.
  2. The following panel should appear:
Changed:
<
<
VELOC_DCS_LV_TOP.JPG
>
>
VELOC_DCS_LV_TOP.PNG
 
  1. If the button next to VELOC_DCS_LV_ConfDB is NOT_READY then click this button.
Changed:
<
<
VELOC_DCS_LV_ConfDB.JPG
>
>
VELOC_DCS_LV_ConfDB.PNG
  1. The following panel should appear. Click Send PHYSICS.
    VELOC_DCS_LV_ConfDB_PHYSICS.PNG
 
  1. The panel should now look like this:
Changed:
<
<
VELO_DCS_LV_OFF.JPG
>
>
VELO_DCS_LV_OFF.PNG
 
  1. Switch on the 48V supply - click on button next to VELOC_DCS_LV_PS
Changed:
<
<
VELOC_DCS_LV_PS.JPG
>
>
VELOC_DCS_LV_PS.JPG
  1. Send the RUN_TYPE PHYSICS.
    VELOC_DCS_LV_PS_PHYSICS.PNG
 
  1. VELOC_DCS_LV_PS should now be READY.
Changed:
<
<
VELOC_DCS_LV_PS_READY.JPG
>
>
VELOC_DCS_LV_PS_READY.PNG
 
Changed:
<
<

-- MarkTobin - 02 Apr 2008

>
>
-- MarkTobin - 29 Apr 2008
 
META FILEATTACHMENT attachment="VELOC_DCS_LV_PS.JPG" attr="" comment="" date="1207148465" name="VELOC_DCS_LV_PS.JPG" path="VELOC_DCS_LV_PS.JPG" size="115931" stream="VELOC_DCS_LV_PS.JPG" user="Main.MarkTobin" version="1"

Revision 22008-04-22 - MarkTobin

Line: 1 to 1
 
META TOPICPARENT name="VELOLVBasic"

Getting Started

  1. Log on to windows terminal in the online network.
  2. Open the directory G:\online\ecs\Shortcuts\VELO
  3. Double click on VEDCSHV_UI_FSM
Changed:
<
<
  1. The following window appears: VEDCSHV_UI_FSM.JPG
>
>
  1. The following window appears: VEDCSHV_UI_FSM.JPG
 
  1. To operate a module on the C side rightclick on VELOC_DCS
    VELOC_DCS_TOP.JPG
  2. Take control of the project by clicking on the padlock next to VELOC_DCS on the panel.

Revision 12008-04-02 - MarkTobin

Line: 1 to 1
Added:
>
>
META TOPICPARENT name="VELOLVBasic"

Getting Started

  1. Log on to windows terminal in the online network.
  2. Open the directory G:\online\ecs\Shortcuts\VELO
  3. Double click on VEDCSHV_UI_FSM
  4. The following window appears: VEDCSHV_UI_FSM.JPG
  5. To operate a module on the C side rightclick on VELOC_DCS
    VELOC_DCS_TOP.JPG
  6. Take control of the project by clicking on the padlock next to VELOC_DCS on the panel.
    VELOC_DCS_TAKE.JPG
  7. Double click on the VELOC_DCS_LV button.
  8. The following panel should appear:
    VELOC_DCS_LV_TOP.JPG
  9. If the button next to VELOC_DCS_LV_ConfDB is NOT_READY then click this button.
    VELOC_DCS_LV_ConfDB.JPG
  10. The panel should now look like this:
    VELO_DCS_LV_OFF.JPG
  11. Switch on the 48V supply - click on button next to VELOC_DCS_LV_PS
    VELOC_DCS_LV_PS.JPG
  12. VELOC_DCS_LV_PS should now be READY.
    VELOC_DCS_LV_PS_READY.JPG

-- MarkTobin - 02 Apr 2008