Date |
Hour |
ID |
Note |
Mon 16/Jan/06 |
18:00 |
GG |
ALARM after 1h of RUN. Liquid weight ~ 12 kg form initial 28 kg. Problem generated by low power in the dummies staves. After recovering system works. |
19:30 |
GG |
RECOVERING. |
Tue 17/Feb/06 |
8:30 |
GG |
Weight 26.9 kg. |
12:00 |
GG |
Weight 27.6 kg. |
16:00 |
GG |
Weight 27.8 kg. Parameter r13 of chiller (=minimum summer setpoint) reduced at 5°C. |
17:30 |
GG |
Weight 27.8 kg. Parameter of the chiller for the defrost temperature changed: A2 from 2 to 1 and A1 from 4 to 3.5. No change: alarm A1 still after few second of cooling. STOP. |
Wed 18/Feb/06 |
15:10 |
GG |
Weight 27.8 kg. RUN with line 9 and 10 opened. |
15:15 |
GG |
Dummy staves ON. |
15:30 |
GG |
Line 2 opened. Weight 20.5 kg. |
16:23 |
GG |
Weight linear decrease: 17.1 kg. |
17:07 |
GG |
Weight 14.6 kg. Stop dummy staves. RECOVERING. |
Thu 19/Feb/06 |
10:33 |
GG |
Weight 27.8 kg. RUN. |
10:55 |
GG |
Opened loop 2. Weight 19.9 kg. Dummy staves are detaching. |
12:00 |
GG |
Weight 15.5 kg. Dummy staves OFF. RECOVERING. |
Fri 20/Jan/06 |
9:30 |
GG |
Weight 27.7 kg. STOP. |
10:00 |
GG |
RUN. |
10:20 |
GG |
Weight 19.2 kg. |
11:10 |
GG |
Power cut of the system: central switch was OFF! RECOVERING. |
11:27 |
GG |
RUN. |
11:42 |
GG |
Opened loop 2. |
12:34 |
GG |
Closed loop 2. RECOVERING. |
Mon 23/Jan/06 |
Morning |
GG |
Reglued dummy staves. Used ARALDIT RAPID. |
Tue 24/Jan/06 |
9:45 |
GG |
RUN. |
9:50 |
GG |
Dummy staves ON. Dummy staves detached where no ARALDIT had been deposed. Dummy staves at 10V->2.8A, system in RECOVERING. ARALDIT deposed "everywhere". |
14:35 |
GG |
Weight 27 kg. RUN. |
14:47 |
GG |
Dummy staves ON. Weight 20.7 kg. |
15:38 |
GG |
Weight 20.4 kg stable for 20'. Opened loop 2. Weight 19.6 kg. |
16:12 |
GG |
Weight 17.7 kg. Linearly decreasing. |
16:48 |
GG |
Weight 15.7 kg. Linearly decreasing. ~ 4 kg/h. |
18:14 |
GG |
Weight 12.5 kg. No more linear decrease. |
19:07 |
GG |
RECOVERING. |
Wed 25/Jan/06 |
15:10 |
GG |
STOP. Weight 27.2 kg. Chiller parameters modifications. b00 from 0 to 1 (display the temperature coming from the evaporator and not the goint to one); r06 from 0 to 1 (setpoint is the temperature coming form the evaporator); r02 from 1 to 5 (chiller ON between the temperature [setpoint, setpoint+r02], currently is [5, 10]. No more alarm A01. |
Thu 26/Jan/06 |
15:55 |
GG |
Difference of ~ 1°C between the temperature of the water out of t chiller end the water entering in the condenser. Chiller from 10°C to 5°C in ~ 2'; from 5°C to 10°C in ~ 14' (cooling dependant). |
18:20 |
GG |
Liquid pressure from 2.725 to 2.700 b. |
18:41 |
GG |
Liquid stable at 12.2 kg since ~ 18:15 |
19:30 |
GG |
RECOVERING. |
Tue 31/Jan/06 |
15:00 |
GG |
System found switched OFF, like 20/01/06. Switched ON. |
15:04 |
GG |
RECOVERING. Weight 26.4 kg. |
15:18 |
GG |
LEAK CONTROL started. See paper logbook for the values. Weight 26.6 kg. |
15:48 |
GG |
All loops have high loss! |
15:57 |
GG |
Second leak control. |
16:30 |
GG |
All loops have high loss! |
16:50 |
GG |
All channels locked and RECOVERING to see eventual variation. |
17:20 |
GG |
Return pressure is 0.39 +/- 0.01 b in all channels. |