Dry air must be flushed in the detector SiPM cold boxes and inside the cooling manifold to avoid condensation/frost.
According to the specification https://edms.cern.ch/document/335007/1.0, the compressed air distributed in the LHC tunnel is good for this application. The dew point is -40 C.
An outlet of the compressed air distribution line was installed next to the BGV (Jan 2015)
The air distribution chain was installed and put into exploitation in September 2015 (TS2)
Air distribution chain
The BGV air distribution system was developed together with EN-CV
The layout was designed and the system components were chosen together with Francisco Josa (EN-CV-DOW)
The functional specification are given in separate section below
Documentation
All components are from FESTO. The order, made by Francisco, can be seen here
The mapping between the Air manifold valves and the Detector modules is given in the Section "Operational aspects" below.
Functional specification
This document discusses the requirements (e.g. the needed flow of air)
Initially considered layout:
The air inputs of the detector modules and manifold are shown in the models below
The detector drawing below is outdated -- in practice there is no serial connection between modules, meaning that each module has 2 independent supply lines
The direction of flow is important. For details, see the document above.
Operational aspects
As discussed in the document above, the needed air flow is:
720 l/hour = 12 l/min in total (16*20 + 400 l/hour)
20+1 individual valves allow to adjust the flow through each output of the air manifold
The total flow going out of the manifold can be adjusted by rotating the cylinder located at the bottom of the pressure regulator (the third element on the plate)
Flow settings 14-10-2015 (Bernd)
Total flow: 30 l/min
Flow into cooling manifold: ~10 l/min (two tubes)
Flow for all 16 SiPM arrays: ~20 l/min (test done opening only one valve at the same time: about 1 l/min)
Mapping between the Air manifold valves and the Detector modules