Temperatures, relative humidity and condensation status in Sector 7-8, Wed 2.

Position T [C] T_meteo [C] RH_meteo [%] Condensation Comments
DFBMA          
120A-4 14     No Setpoint 40K - add_heaters
120A-8 13     No Setpoint 50K - add_heaters
6kA 8 (on top of G11)   Yes No on chimneys - Setpoint 50K
DFBMC   20.5 44.2    
6kA 8 (on G11)   No Setpoint 70K
120A-8 11     No Setpoint 50KC - add-heaters Notworking
120A-4 11     No Setpoint 40K - add-heaters Notworking
DFBAO_LCM          
Q6_L8 (120A) 8     Yes  
DFBAO_HCM          
Q9_L8 (60A) 12     No  
Q10_L8 (60A) 11     No  
Q11_L8 (60A) 10     No  
Q12_L8 (60A) 9 18.3 49.5 Yes  
Q13_L8 (60A) 11     No  
Q14_L8 (60A) 9     Yes  
Q15_L8 (60A) 10     Yes  
Q20_L8 (60A) 9     Yes  
Q25_L8 (60A) 11     Yes  
Q30_L8 (60A) 11     Yes  
Q30_R7 (60A) 10     -  
Q25_R7 (60A) 11     -  
Q20_R7 (60A) 10     No  
Q15_R7 (60A) 9     Yes  
Q14_R7 (60A) 9     Yes  
Q13_R7 (60A) 15?     No  
Q12_R7 (60A) 10 17.3 53.4 Yes  
Q11_R7 (60A) 9     Yes  
Q10_R7 (60A) 9     Yes  
Q9_R7 (60A) 10     No  
Q8_R7 (60A) 9     Yes  
Q7_R7 (60A) 9     Yes  
DFBAN   18 49.9 Yes  
600A 10     Yes Setpoint 150K
13kA 10     Yes Setpoint 110K
DFBMH       No  
600A 11     No Setpoint 120K