TWiki home | Point 1 | Point 2 | Point 3 | Point 4 | Point 5 | Point 6 | Point 7 | Point 8 | Minutes |
Created by Main.MirkoPojer on 2007-05-04 - 23:08
Position | T [°C] | T_meteo [°C] | RH_meteo [%] | T_portable [°C] | RH_portable [%] | Condensation | Dew Point [°C] | Air Speed [m/s] | Time |
---|---|---|---|---|---|---|---|---|---|
DFBMC | 20.4 | 48.1 | 0.3-0.8 | 17.30 | |||||
20.4 | 48.3 | 20.1 | 51.1 | 19.30 | |||||
Q6_L8 (120A) | 8.5 | 19.7 | 53.1 | Low | 9.9 | ||||
Q8_L8 (120A) | 9 | 19.8 | 53.2 | Low | 10.0 | ||||
Q9_L8 (120A) | 10 | 19.3 | 54.4 | No | 10.0 | 1.1-1.4 | |||
Q10_L8 (120A) | 9 | 19.0 | 54.2 | Low | 9.5 | 18.50 | |||
Q11_L8 (60A) | 9 | 19.0 | 54.6 | No | 9.5 | ||||
Q12_L8 (60A) | 9 | 18.5 | 52 | 18.6 | 54.5 | Yes | 9.2 | 1.0-1.3 | |
Q13_L8 (60A) | 10 | 18.4 | 55.2 | No | 9.2 | ||||
Q14_L8 (60A) | 9 | 18.5 | 55.1 | Yes | 9.3 | ||||
Q15_L8 (60A) | 8.5 | 18.2 | 55.9 | Yes | 9.2 | 19.15 |
Edit, attach file or add comment
Created by Main.JacekSzkutnik on 2007-05-04 - 18:35
DFBAO | RQ6.L8B1 RQ6.L8B2 |
Switch on the flashing lights around the chimneys of RQ6.L8 circuit in the DFBAO | HCC |
Unlock and switch on the RPHGB.UA83.RQ6.L8B1 and RPHGB.UA83.RQ6.L8B2 converters. | AB/PO |
||
Sequencer tests on powering procedures for 6kA magnets with 2 PCs ("Q4Q5" procedure) | AB/CO |
DFBMC | RCBCH5.L8B1 RCBCV5.L8B2 |
Balisage with flashing lights | HCC |
PC Configuration (test of PC and magnet at minimum current) | AB/PO | ||
RQ5.L8 | Unlock of the quench heater power supplies (DQHDS) of Q5 and charge. | AT/MEL | |
PC Configuration | AB/PO | ||
RCBCH5.L8B1 RCBCV5.L8B2 RQ5.L8 |
PIC2 | HCC AB/CO AB/PO AT/MEL AT/ACR |
|
P2N | HCC AB/CO AB/PO AT/MEL AT/ACR |
PC_Config | PNO.1 | PNO.2 | PNO.3 | ||
---|---|---|---|---|---|
RCBH11_L8B1 | X | X | X | X | |
RCBV11_L8B2 | X | X | X | X | |
RCBH12_L8B2 | X | X | X | O | |
RCBV12_L8B1 | X | X | X | O | |
RCBH13_L8B1 | X | X | X | O | |
RCBV13_L8B2 | X | X | X | O | |
RCBH14_L8B2 | X | X | X | O | |
RCBV14_L8B1 | X | X | X | O | |
RCBH15_L8B1 | X | X | O | O | |
RCBV15_L8B2 | X | X | O | O | |
RCBH16_L8B2 | X | X | O | O | |
RCBV16_L8B1 | X | X | O | O | |
RCBH17_L8B1 | - | PC_Config/crowbar tests to be repeated | |||
RCBV17_L8B2 | - | PC_Config/crowbar tests to be repeated | |||
RCBH18_L8B2 | - | PC_Config/crowbar tests to be repeated | |||
RCBV18_L8B1 | - | PC_Config/crowbar tests to be repeated | |||
RCBH23_L8B1 | O | ||||
RCBV23_L8B2 | O | ||||
RCBH24_L8B2 | O | ||||
RCBV24_L8B1 | O | ||||
RCBH25_L8B1 | |||||
RCBV25_L8B2 | |||||
RCBH27_L8B1 | |||||
RCBV27_L8B2 | |||||
RCBH28_L8B2 | |||||
RCBV28_L8B1 | |||||
RCBH29_L8B1 | |||||
RCBV29_L8B2 | |||||
RCBH31_L8B1 | |||||
RCBV31_L8B2 | |||||
RCBH32_L8B2 | |||||
RCBV32_L8B1 |
PC_Config | PIC2 | PNO.1 | PNO.2 | PNO.3 | PNO.4 | ||
---|---|---|---|---|---|---|---|
RCBCH9_L8B1 | - | PC_Config/crowbar tests and TFA missing | |||||
RCBCV9_L8B2 | - | PC_Config/crowbar tests and TFA missing | |||||
RCBCH10_L8B2 | - | PC_Config/crowbar tests and TFA missing | |||||
RCBCV10_L8B1 | - | PC_Config/crowbar tests and TFA missing |
DFBMC | RCBCH5.L8B1 RCBCV5.L8B2 |
Connection of the DC cables to the power converters for these circuits (before 9:00) | AB/PO |
Verification of the connections at the DFBMC side | AT/MEL | ||
DFBAO | RQ6.L8B1 RQ6.L8B2 |
Switch on the flashing lights around the chimneys of RQ6.L8 circuit in the DFBAO | HCC |
Unlock and switch on the RPHGB.UA83.RQ6.L8B1 and RPHGB.UA83.RQ6.L8B2 converters. | AB/PO |
||
Sequencer tests on powering procedures for 6kA magnets with 2 PCs ("Q4Q5" procedure) | AB/CO |
Edit, attach file or add comment
Created by Main.MikeKoratzinos on 2007-05-04 - 16:35
Edit, attach file or add comment