OPC-UA communication
The OPC-UA server will run on the ELMBs CCPC (TBC). In the
ComLab, the pclhcb33 machine is emulating this CCPC. You need to change the tcp point of the OPC server under System Management -> Driver OPC -> OPC UA client of the
R2DCS1 project to point to pclhcb33.
Voltage devices
Humidity and pressure sensors are declared under the corresponding ELMB node as Direct ADC Voltage devices. The converted values are obtained by declaring the devices under the
AnalogDigital node in the D&N, and by setting the corresponding DP function config.
Alarm settings
Following the LHCb ECS guidelines, not acknowledgeable alarms will be used (_fwFatalNack (ERROR), _fwErrorNack (Too Low), _fwWarningNack (WARNING)).
Temperatures (value) limits: 5, 30, 40
Humidity limits: 5, 50, 70
Archives settings
LV (
MeasurementSenseVoltage,
MeasurementCurrent): Deadband AND time: 30 minutes, 0.5 absolute value.
Temperatures (value): Deadband AND time: 30 minutes, 0.5 degrees.
Raw voltages (value): Deadband AND time: 30 minutes, 1 mV.
Converted values (AI: humidities, pressures...): Deadband AND time: 30 minutes, 0.5 absolute value.
--
GiovanniCavallero - 2019-09-05